High Voltage Integrated Vacuum Circuit Breaker

Send Inquiry
High Voltage Integrated Vacuum Circuit Breaker
Details
Faults are common in 10 kV overhead distribution lines. At present, most outdoor pole-mounted circuit breakers used in distribution networks adopt external disconnectors integrated with the switch.
Category
Circuit Breaker
Share to
Description

Products Description

 

Based on years of industry experience, most failures of outdoor circuit breakers are caused by the external disconnector and the PT. To address these issues, our company has developed the ZW32N-12/630G-20 deeply integrated pole-mounted vacuum circuit breaker (with built-in isolation).

This High Voltage Integrated Vacuum Circuit Breaker is outdoor distribution equipment with a rated voltage of 12 kV and is suitable for three-phase AC 50 Hz power systems.

The High Voltage Integrated Vacuum Circuit Breaker adopts mature silicone rubber composite epoxy resin APG technology, integrating current sensors, voltage sensors, live-line display indicators, PT primary terminals, vacuum interrupters, and disconnectors into a fully sealed pole column.

This design achieves deep integration of the pole-mounted circuit breaker, providing comprehensive functions such as measurement, protection, and synchronous line loss monitoring. Only a single cable is required to connect to the feeder terminal unit (FTU), making on-site installation simple and convenient.

product-800-800

Because the contact blades and contacts are exposed to outdoor environments for long periods, the contact points are prone to oxidation. In addition, the mechanical interlock has a long transmission path, making it susceptible to jamming, and it cannot be equipped with an electrical interlock. The primary wiring of the PT (potential transformer) is also exposed, resulting in serious oxidation and corrosion.

 

Key Technical Parameters

 

No.

Item

Parameter

1

Rated Voltage

12kV

2

Rated Current

630A

3

Withstand Voltage of Power Frequency (1min) - Phase-to-Phase, Phase-to-Earth / Across Open Contacts

42/48kV

4

Lightning Impulse Withstand Voltage (Peak) - Phase-to-Phase, Phase-to-Earth / Across Open Contacts

75/85kV

5

Partial Discharge

≤ 20pC at 14.4kV

6

Rated Voltage

Phase Voltage Ratio: (10kV/√3) / (3.25V/√3)
Zero-Sequence Voltage Ratio: (10kV/√3) / (6.5V/3)

7

Accuracy Class

Phase Voltage Accuracy: 0.5 (3P) Class
Zero-Sequence Voltage Accuracy: 1 (3P) Class

8

Operating Frequency

50±2.5Hz

9

Rated Current

Phase Current Ratio: 600A / 1V
Zero-Sequence Current Ratio: 20A / 0.2V

10

Accuracy Class

Phase Current Accuracy: 0.5S (5P) Class
Zero-Sequence Current Accuracy: 1 (10P) Class

11

Ambient Temperature

-40℃~+45℃

 

Detailed images

 

product-800-800

 

Hot Tags: high voltage integrated vacuum circuit breaker, China high voltage integrated vacuum circuit breaker manufacturers, suppliers, factory, Intelligent Integrated Vacuum Circuit Breaker, Electronic Circuit Breaker, 10KV Vacuum Circuit Breaker, circuit breaker, Outdoor High Voltage Circuit Breaker, High Voltage Integrated Vacuum Circuit Breaker

Send Inquiry