Products Description
The 27kV Interlocking Recloser features excellent core performance indicators, including a rated current of 630 A, enabling it to reliably meet the conventional power transmission requirements of medium- and high-voltage distribution networks. It has a rated short-circuit breaking current of 16 kA, a rated short-circuit making current and rated peak withstand current of 40 kA, and a rated short-time withstand current of 16 kA for 3 seconds.
These characteristics allow the recloser to rapidly activate protection functions during short-circuit faults, reliably interrupt fault currents, withstand short-duration impact currents, and quickly restore power supply through its linked reclosing function, significantly reducing economic losses and user inconvenience caused by power outages.
The operating performance is precise and controllable, strictly following the rated operating sequence of "O–0.2 s–CO–2 s–CO–2 s–CO–2 s–CO." Closing and opening simultaneity is controlled within ≤2 ms, contact bounce is ≤3 ms, the closing time is ≤60 ms, and the opening time is ≤40 ms. The device operates electrically with a rated control voltage of DC 220 V, providing sensitive response and efficient control.
The insulation protection capability meets high industry standards. The 1-minute power-frequency withstand voltage (RMS) for switch contacts, phase-to-phase, and phase-to-ground is 60 kV, while the lightning impulse withstand voltage (peak) for the same insulation paths reaches 150 kV. Partial discharge is ≤10 pC at a test voltage of 1.2Ur/√3. These features effectively protect against overvoltage and partial discharge risks, ensuring insulation safety and long-term stable operation in complex outdoor environments.

The 27kV Interlocking Recloser has a wide range of applications and is well suited for urban medium- and high-voltage distribution network upgrades, smart substation construction, industrial park distribution system renovation, support for new energy power station grid connection, and rural power grid modernization projects. It meets the protection and control requirements of traditional distribution networks while aligning with the development trend toward automation and interconnection in smart grids, laying a solid technical foundation for the safe, continuous, and efficient operation of power systems.
Main Technical Parameters
|
No. |
Parameter Type |
Standard Value |
Remarks |
|
|
1.1 |
||||
|
1.2 |
Rated Voltage |
27kV |
||
|
1.3 |
System Nominal Frequency |
50Hz |
||
|
1.4 |
Rated Current |
630A |
||
|
1.5 |
Rated Short-circuit Breaking Current |
16kA |
||
|
1.6 |
Rated Short-circuit Making Current |
40kA |
||
|
1.7 |
Rated Peak Withstand Current |
40kA |
||
|
1.8 |
Rated Short-time Withstand Current and Duration |
16kA/3s |
||
|
1.9 |
Rated Operating Sequence |
O-0.2s-CO-2s- CO-2s-CO-2s-CO |
||
|
1.14 |
Mechanical Life |
≥10000time |
||
|
1.15 |
Number of Operating Cycles at Rated Current |
≥500time |
||
|
1.16 |
Closing Asynchronism |
≤2ms |
||
|
1.17 |
Opening Asynchronism |
≤2ms |
||
|
1.18 |
Contact Bounce |
≤3ms |
||
|
1.19 |
Closing Time |
≤60ms |
||
|
1.20 |
Opening Time |
≤40ms |
||
|
1.21 |
Power-frequency Withstand Voltage (1 min) - RMS Value |
Switch Disconnecting Port |
60 |
|
|
1.22 |
Phase-to-Phase,Phase-to-Ground |
60 |
||
|
1.23 |
Lightning Impulse Withstand Voltage - Peak Value |
Switch Disconnecting Port |
150 |
|
|
1.24 |
Phase-to-Phase,Phase-to-Ground |
150 |
||
|
1.25 |
Partial Discharge (1.2Ur/√3) |
≤10 pC |
||
|
2 |
Permanent Magnetic Actuator |
|||
|
2.1 |
Operating Mechanism |
Permanent Magnet |
||
|
2.2 |
Operation Mode |
Electric |
||
|
2.3 |
Rated Voltage |
DC220V |
||
Hot Tags: 27kv interlocking recloser, China 27kv interlocking recloser manufacturers, suppliers, factory, 15kV Interlocking Recloser, recloser, 24kV Auto Circuit Recloser, 27kV Interlocking Recloser, 27kV Load Break Switch, 27kV Auto Recloser