Products Description
It adopts a pillar-type three-phase solid-sealed pole integrated structure, with current transformers and voltage sensors integrated inside the poles. Combined with a permanent-magnet operating mechanism and a three-phase linkage transmission system, it achieves synchronous and coordinated operation of all three phases.
The device supports both electric opening and closing as well as manual tripping modes. The manual tripping mechanism is equipped with a mechanical interlock to prevent misoperation, and a built-in mechanical counter displays the number of opening and closing operations in real time.
It has an IP65 protection rating and a mechanical life of no less than 10,000 operating cycles, making it a key piece of equipment for promoting smart grid upgrades and ensuring safe and stable power supply. The Interlock type Recloser uses vacuum as the arc-extinguishing medium, providing efficient and reliable arc-extinguishing performance.
The rated breaking current is 16 kA, the rated short-time withstand current is 16 kA for 3 seconds, and the rated short-circuit breaking capacity is not less than 30 operations. The device can respond rapidly to short-circuit faults, accurately interrupt fault currents, and quickly restore power supply through its linkage reclosing function, significantly reducing power outage losses.

The insulation performance meets high standards for high-voltage equipment, with a rated power-frequency withstand voltage of 70 kV across the contact gap and a rated lightning impulse withstand voltage of 170 kV phase-to-ground and phase-to-phase. The minimum external creepage distance is 31 mm/kV, enabling the equipment to withstand grid overvoltage surges and harsh environmental conditions such as high temperature, high humidity, and dust, thereby ensuring long-term stable operation.
The operating design balances safety and convenience, following the scientific operating sequence of "O-0.5 s-CO-2 s-CO-5 s-CO." The operations are coordinated and precise, and the mechanical interlock and operation counter associated with manual tripping enhance operational safety while allowing maintenance personnel to monitor equipment status in real time.
The Interlock type Recloser are widely used in high-voltage distribution network upgrades, large-scale intelligent substation construction, high-voltage power distribution systems in industrial parks, grid-connection projects for new energy power plants, and long-distance power transmission projects. They meet the core protection and control requirements of high-voltage power systems while aligning with the development trends of intelligent grid automation and safety, laying a solid foundation for the continuous, efficient, and safe operation of power systems.
Main Technical Parameters
|
No. |
Item |
Unit |
Standard Value |
|
|
1 |
Model |
WE-CHZ-38/800-16 |
||
|
2 |
Structure |
Post type |
||
|
3 |
Arc Extinguishing Medium |
Vacuum |
||
|
4 |
Rated Voltage (Highest System Voltage) |
kV |
38 |
|
|
5 |
Rated Current |
A |
800 |
|
|
6 |
Rated Breaking Current |
kA |
16 |
|
|
7 |
Rated Power-Frequency Withstand Voltage |
across open contacts |
kV |
70 |
|
8 |
Rated Lightning Impulse Withstand Voltage |
Phase-to-Earth / Phase-to-Phase |
kV |
170 |
|
9 |
Rated Short-time Withstand Current and Duration |
kA/s |
16/3 |
|
|
10 |
Mechanical Life |
Operations |
≥10000 |
|
|
11 |
Minimum Creepage Distance of External Insulation |
mm |
31mm/kV |
|
|
12 |
Number of Rated Short-circuit Breaking Operations |
Times |
≥ 30 times |
|
|
13 |
Type or Model of Operating Mechanism |
Permanent Magnet |
||
|
14 |
Operation Mode |
Electric Close & Open + Manual Open |
||
|
15 |
Operating Sequence |
O - 0.5s - CO - 2s - CO - 5s - CO |
||
|
16 |
Recloser Protection Class |
IP65 |
||
Hot Tags: 38kv interlock type recloser, China 38kv interlock type recloser manufacturers, suppliers, factory, 15kV Interlocking Recloser, recloser, 24kV Auto Circuit Recloser, 27kV Interlocking Recloser, 27kV Load Break Switch, 27kV Auto Recloser