Products Description
The device features an IP67 protection rating and a mechanical life of no less than 10,000 operations. The enclosure adopts the standard RAL 7042 color, combining practicality with aesthetics, making it a key piece of equipment for improving grid intelligence and enhancing user experience.
The 24kV Auto Circuit Recloser delivers excellent core performance, with a rated current of 630 A, a rated short-circuit breaking current of 20 kA, and a rated short-circuit making current and rated peak withstand current of 50 kA.
The rated short-time withstand current is 20 kA for 4 seconds. It can respond rapidly to short-circuit faults, reliably making and breaking fault currents, and effectively restoring power through its automatic reclosing function, thereby reducing outage losses.
The rated cable charging breaking current is 25 A, and temperature rise limits strictly comply with the GB/T 11022 standard, ensuring stable operation under various working conditions.

Operating performance is precise and efficient, following the rated operating sequence of "Open – 0.3 s – Close-Open – 180 s – Close-Open." Closing and opening simultaneity is ≤ 2 ms, contact bounce time is ≤ 2 ms, closing time of the spring operating mechanism is ≤ 60 ms, opening time is ≤ 40 ms, energy storage time is ≤ 15 s, energy storage power is ≤ 240 W, and instantaneous switching power is ≤ 380 W. The operating mode supports both electric and manual operation and is compatible with a DC 24 V rated control voltage, flexibly meeting different operational requirements.
Insulation performance meets high industry standards, with a 1-minute power-frequency withstand voltage (RMS) of 79 kV across the switch contacts and 65 kV between phases and to ground. The lightning impulse withstand voltage (peak) is 145 kV across the switch contacts and 125 kV between phases and to ground, effectively resisting overvoltage surges.
The 24kV Auto Circuit Recloser is widely used in urban medium- and high-voltage distribution networks, smart substations, industrial park distribution systems, new energy power plant grid-connection projects, and rural power grid upgrading and renovation projects. It meets the protection and control requirements of traditional distribution networks while aligning with the automation and efficiency trends of smart grids, providing strong support for the safe, continuous, and stable operation of power systems.
Main Technical Parameters
|
No. |
Parameter Type |
Standard Parameter Value |
Remarks |
||
|
1.1 |
Cabinet Color |
RAL7042 |
|||
|
1.2 |
System Nominal Voltage |
24kV |
|||
|
1.3 |
System Nominal Frequency |
50Hz |
|||
|
1.4 |
Rated Current |
630A |
|||
|
1.5 |
Rated Short-circuit Breaking Current |
20kA |
|||
|
1.6 |
Rated Short-circuit Making Current |
50kA |
|||
|
1.7 |
Rated Peak Withstand Current |
50kA |
|||
|
1.8 |
Rated Short-time Withstand Current and Duration |
20kA/4s |
|||
|
1.9 |
Rated Operating Sequence |
O - 0.3s - CO - 180s - CO |
|||
|
1.10 |
Rated Cable Charging Breaking Current |
25A |
|||
|
1.11 |
Temperature Rise Limits |
In accordance with GB/T 11022 |
|||
|
1.12 |
Mechanical Life |
≥ 10,000 times |
|||
|
1.13 |
Rated Short-circuit Current Breaking Times |
≥ 30 times |
|||
|
1.14 |
Closing Asynchronism |
≤2ms |
|||
|
1.15 |
Opening Asynchronism |
≤2ms |
|||
|
1.16 |
Contact Bounce |
≤2ms |
|||
|
1.17 |
Closing Time |
≤ 60 ms (Spring) |
|||
|
1.18 |
Opening Time |
≤ 40 ms (Spring) |
|||
|
1.19 |
Power-frequency Withstand Voltage (RMS Value) for 1 min |
Switch Disconnecting Gap |
79 |
||
|
1.20 |
Phase to Phase |
65 |
|||
|
1.21 |
Lightning Impulse Withstand Voltage (Peak Value) |
Switch Disconnecting Gap |
145 |
||
|
1.22 |
Phase to Phase |
125 |
|||
|
2 |
Operating Mechanism |
||||
|
2.1 |
Operating Mechanism |
Spring |
|||
|
2.2 |
Operating Mode |
Motor and Manual |
|||
|
2.3 |
Rated Voltage |
DC24V |
|||
|
2.4 |
Charging Time |
≤ 15 s (Spring) |
|||
|
2.5 |
Charging Power |
≤ 240 W (Spring) |
|||
|
2.6 |
Instantaneous Making and Breaking Power |
≤ 380 W (Spring) |
|||
Hot Tags: 24kv auto circuit recloser, China 24kv auto circuit recloser manufacturers, suppliers, factory, 15kV Interlocking Recloser, recloser, 24kV Auto Circuit Recloser, 27kV Interlocking Recloser, 27kV Load Break Switch, 27kV Auto Recloser